PLC WECON LX5S Series / PLC LX5S-2424MR-(AN/DN) (Relay output) / IO: 24xDI/24xDO , Interface Port : RS422, RS485, Ethernet and 1 BD board supported.
Type
I/O Points
Output type
Power supply
หมวดหมู่ : FACTORY AUTOMATION ,  PLC & Modules ,  CPU , 
แบรนด์ : WECON
Share
| Technical information | |
| Running mode | Round scan / Interrupt | 
| Programming | Instruction list / Ladder | 
| Total instructions | Basic Instructions: 29 / Applied Instruction: 170 | 
| Execute time | Basic Instructions: 0.03-0.08us | 
| System Storage | 512Kbyte | 
| Download/ Monitoring | Serial Programming Cable / Micro USB | 
| External Interrupt | 6 Channels | 
| Timer Interrupt | 100 Channels ; support 0.1ms interrupt | 
| High Speed Input | 2 channel 150K Hz | 
| 4 channel 10KHz | |
| High Speed Input AB Phase | 1 channel 100K Hz, supports 2 or 4 frequency times | 
| 2 channels 10K Hz, supports 2 or 4 frequency times | |
| Holding Addresses | Adjustable | 
| Storage | FLASH | 
| Filter | For all X input terminals | 
| Electrical data | |
| Supply voltage | AC type 85..265VAC 50..60Hz ; DC type 24VDC ±10% | 
| Power consumption | AC type ≤60W ; DC type ≤30W | 
| Power Outage Time | 10ms | 
| Power Fuse | 250V 3.15A | 
| Rush Current | AC Type <15A 5ms / AC 100V; <30A 5ms / AC 200V | 
| DC type <15A 1ms / DC 24V | |
| Power Output | AC Type DC 24V 850mA ; DC type N/A | 
| Backup battery | YES | 
| Outputs | |
| Digital input Power Supply | DC 24V | 
| Output Mode | Relay | 
| Output function | dry contact | 
| Output Circuit | AC 250VAC ; DC 30VDC | 
| Common output current | N/A | 
| Insulation | Mechanistic | 
| Leak current | N/A | 
| Min. Load | N/A | 
| Max.Load | Resistive ; 2A point 8A COM port | 
| Inductive ; 80VA | |
| General ; 100W | |
| Response Time | <10ms | 
| High Speed Pulse Output | N/A | 
| Operating environment | |
| Ambient temperature [°C] | 0..55 | 
| Storage temperature [°C] | -20..70 | 
| Ambient humidity [%RH] | 35..85 | 
| Protection | IP20 | 
| Tests / approvals | |
| Shock Resistance | JIS C 0040 Standard | 
| Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard | 
| Noise voltage amplitude 1KVP-P | |
| pulse width 10us, period 0.3 s, edge time 5ns, duration 1min. | |
| Vibration resistance | 10…50Hz (1.5mm) | 
| Approval | CE , FCC , ISO9001 | 
| Mechanical data | |
| Housing material | ABS | 
| Mounting | DIN-Rail | 
| Dimensions [mm] | 175 x 107 x 87 | 
| Connection I/O | Terminal | 
| Software / Interface | |
| Software | Wecon PLC Editor1/2 | 
| Interface port | COM1 RS422/RS485 ; COM2 RS485 ; 1x Ethernet | 
| Protocol | WECON protocol / Modbus RTU | 
_______________________________________________________________________________________________
LX5S DATASHEET                                                                                                               Download
____________________________________________________________________________________________________